The series JCZ-5 of high-voltage vacuum contactor are suitable for the distribution system of metallurgy, mine, petro-chemistry and building, to control the equipments used eletricity such as high-voltage motor of 6kV or under 6kV, transformer and capacitive loading etc. Especially suitable for frequent operation domain. Because of its small volume, light weight and packaged design of upper and lower arrangement, prevalented in the world. It is convenient to use and main tain, and is easy to form the complete equipment of F-C loop.
www.wvs-tech.de - vakuum schütze - seitenskizze  von serie jcz5-7.2j und jzc5-12j www.wvs-tech.de - vakuum schütze - frontskizze  von serie jcz5-7.2j und jzc5-12j www.wvs-tech.de - vakuum schütze - serie jcz5-7.2j und jzc5-12j

Download PDF-Dokument
Main Technical Parameters  JCZ5-7.2J(D)  JCZ5-12J(D) 
Rated Voltage  7,2kV  12kV 
Rated current  200A 400A 630A 400A 630A
Rated turn-on current  2000A 4000A 6300A 4000A 6300A
Rated interrupted current in maximum  1600A 3200A 5040A 3200A 5040A
Rated operating voltage  110/220VAC 110/220VAC
Contacts Industrial Frequency Bearing Voltage in OFF status 32kV 42kV
Switch-on coil pick-up voltage  ≤DC 6/3A ≤DC 6/3A
Coil and current maintenance  DC 0,32/0,16A DC 0,32/0,16A
Switch-off coil trip current  DC 2,5/1,3A DC 2,5/1,3A
Rated operating frequency  300Hz 300Hz
Mechanical life  30×104 times 30×104 times
Electricity life  AC-3  25×104 times 25×104 times
AC-4  10×104 times 10×104 times
Contact open space  4,5+1-0,5mm 6+1-0,5mm
Super distance  1,5±0,5mm  1,5±0,5mm 
Switch-on average speed  0,15±0,05mm/s 0,2±0,1mm/s
Switch-off average speed  0,45±0,15mm/s  0,6±0,1mm/s 
Three phases switch-on synchronism  ≤2,0ms ≤2,0ms
Contact spring time  ≤5,0ms  ≤5,0ms 
Switch-on time  ≤150ms ≤150ms
Fixed switch-off time  ≤50ms  ≤50ms 
Several phases conductive circuit resistance (20°C) ≤250µΩ ≤250µΩ
Contact spring length in switch-on condition  36±1mm 36±1mm
Weight  about 28kg about 32kg

Rated operating voltage Rated heat current Service life   (times) Usage mode Rated operating current
mechanics electrics DC AC
AC 220V  6A ≥5×106 ≥2×105 DC11 4A 0,4A
DC 380V  6A     AC11     